Weidmüller UR20-4AI-UI-16-DIAG
Add to cart to view estimated shipping cost.
Weidmüller UR20-4AI-UI-16-DIAG / Lenze W540-C-2E-005 — analogue input module, 4-channel, current/voltage, 16-bit resolution, 24 V DC, PUSH IN, IP20, u-remote system, order no. 1315690000. A high-precision 4-channel analogue input module for the u-remote system. Each channel is individually parameterisable for measurement range selection, and each has its own status LED for immediate visual feedback. Sensors can be connected using 2-wire, 3-wire, or 3-wire + FE technology via PUSH IN terminals. The module is short-circuit-proof and reverse-polarity protected, with a sensor supply of up to 750 mA from the input current path (UIN). Both module-level and individual channel diagnostics are supported, with a conversion time of 1 ms per channel. Compatible with all u-remote fieldbus head stations.
Available in stock — ships within 3 days after payment.
Product overview
| Manufacturer | Weidmüller Interface GmbH & Co. KG |
| Type | UR20-4AI-UI-16-DIAG |
| Order number | 1315690000 |
| GTIN (EAN) | 4050118118612 |
| System reference | Lenze W540-C-2E-005 |
| Product type | Remote I/O module, IP20, 4-channel, Analog signals, Input, Current/Voltage, 16-bit, PUSH IN connection |
| Module type | Analogue input module — 4-channel, voltage/current, 16-bit with diagnostics |
| Number of analogue inputs | 4 |
| Resolution | 16 Bit |
| Accuracy | 0.1% FSR |
| Input signal types — voltage | 0…5 V, 0…10 V, 1…5 V, 2…10 V, ±10 V |
| Input signal types — current | 0…20 mA, 4…20 mA |
| Conversion time | 1 ms |
| Response time / fallback time | <50 ms |
| Internal resistance — voltage input | 100 kΩ |
| Internal resistance — current input | 41.2 Ω |
| Sensor supply | Yes — nominal/max. 750 mA |
| Short-circuit-proof | Yes |
| Reverse polarity protection | Yes |
| Module diagnosis | Yes |
| Individual channel diagnosis | Yes |
| Sensor connection | 2-wire, 3-wire, 3-wire + FE |
| Process data | 8 Byte |
| Diagnostic data | 1 Bit |
| Supply voltage | 24 V DC +20% / –15%, via system bus |
| Current consumption from Isys, typ. | 8 mA |
| Current consumption from IIN | 25 mA + sensor feed |
| Galvanic isolation | 500 V DC between the current paths |
| Type of connection | PUSH IN |
| Wire cross-section | 0.14 mm²–1.5 mm² (AWG 26–16), solid and finely stranded |
| Fieldbus protocols | PROFINET IRT/RT, PROFIBUS DP-V1, EtherCAT, Modbus/TCP, EtherNet/IP, CANopen, DeviceNet, POWERLINK, CC-Link, CC-Link IE TSN, IEC 61162-450 |
| Interface | u-remote system bus |
| Transmission speed, max. | 48 Mbit/s |
| Mounting | TS 35 DIN rail |
| Operating temperature | –20°C to +60°C |
| Storage temperature | –40°C to +85°C |
| Dimensions (W × H × D) | 11.5 mm × 120 mm × 76 mm |
| Mounting dimension – height | 128 mm |
| Net weight | 89 g |
| UL 94 flammability rating | V-0 |
| Pollution severity | 2 |
| Test voltage | 500 V |
| Surge voltage category | II |
| Vibration resistance | 5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm amplitude; 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration (IEC 60068-2-6) |
| Shock | 15 g over 11 ms, half sinus wave (IEC 60068-2-27) |
| Air humidity (operation/storage/transport) | 10% to 95%, non-condensing (DIN EN 61131-2) |
| Air pressure (operation) | ≥ 795 hPa (height ≤ 2000 m, DIN EN 61131-2) |
| RoHS compliance | Compliant with exemption (7a, 7cI) |
| REACH SVHC | Lead 7439-92-1 |
| Product Carbon Footprint | 8.503 kg CO₂ eq. (cradle to gate) |
| Approvals / certifications | CE, UKCA, cULus (E141197), cULusEX (E223527), ATEX, IECEx, ClassNK, ABS, DNV, KoreaCert, RoHS compliant |
| Condition | New — in original packaging (OVP) |
Applications
- High-precision analogue sensor acquisition in machine and plant engineering — the module records voltage and current signals from up to 4 sensors simultaneously with 16-bit resolution and 0.1% FSR accuracy, making it suitable for process control applications where measurement quality is critical
- Flexible multi-sensor wiring — each channel independently supports 2-wire, 3-wire, and 3-wire + FE sensor connections via PUSH IN terminals, and measurement range parameters are individually configurable per channel, accommodating mixed sensor types within a single module
- Applications requiring comprehensive diagnostic transparency — individual channel diagnostics, module-level diagnostics, and per-channel status LEDs enable fast fault localisation and minimise unplanned downtime in automated production environments
- Sensor-powered installations — the integrated sensor supply of up to 750 mA from the input current path (UIN) eliminates the need for separate sensor power supplies, reducing wiring complexity and cabinet footprint in decentralised I/O architectures
- Hazardous area installations (ATEX/IECEx) and marine applications (ClassNK, ABS, DNV) requiring a certified, high-resolution analogue input module within the u-remote platform, compatible with all u-remote fieldbus head stations
Shipping
- Ships within 3 days after payment
- Secure packaging for safe industrial transport
- Free delivery within Germany
Warranty & compliance
- 12-month warranty included
- Product is fully compliant with EU industry standards
- VAT invoice included with every order
(GPSR (EU) 2023/988): Contact us at info@liquisto.com for Manufacturer / EU Responsible Party product safety contact details.