Pepperl+Fuchs Frequency Converter with Direction and Synchronization Monitor KFU8-UFT-2.D

  • S/. 1,565.00
    Unit price per 
Shipping calculated at checkout.


PEPPERL+FUCHS Frequency Converter with Direction and Synchronization Monitor KFU8-UFT-2.D

  • 2-channel signal conditioner
  • Universal usage at different power supplies
  • Dry contact or NAMUR inputs
  • Input frequency 1 mHz ... 1 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Configurable by PACTware or keypad
  • Line fault detection (LFD)
  • Signal Type: Digital Input

 

Connection terminals 23, 24
Rated voltage 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Rated current approx. 130 mA
Power dissipation 2.2 W / 3.5 VA
Power consumption 2.5 W / 4 VA

 

Programming interface programming socket

 

Connection side field side
Connection input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Pulse duration min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detection breakage I ≤ 0.15 mA; short-circuit I > 4 mA
Input III, IV
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA

 

Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III and IV signal , electronic output, passive
Contact loading 40 V DC
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: blocked output (off-state current ≤ 10 µA)
Output V analog
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Load max. 650 Ω
Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)

 

Input I and II
Measurement range 0.001 ... 1000 Hz
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring time frequency measurement: < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay ≤ 200 ms
Output V
Resolution < 10 µA
Accuracy < 30 µA
Influence of ambient temperature 0.005 %/K (50 ppm)

 

Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
via PACTware
Labeling space for labeling at the front

 

Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000

 

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

 

Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001

 

Original Packaging
unused excess stock with durability guarantee

produit d'occasion inutilisé avec une garantie de durabilité

nieużywany produkt z gwarancją trwałości

Producto de segunda mano sin usar con durabilidad

prodotto di seconda mano inutilizzato con garanzia di durata

produto em segunda mão não utilizado com garantia de durabilidade

 


We Also Recommend