Weidmüller UR20-4DI-2W-230V-AC
Add to cart to view estimated shipping cost.
Weidmüller UR20-4DI-2W-230V-AC / Lenze W560-C-2E-001 — digital input module, 4-channel, 2-wire, 230 V AC, PUSH IN, IP20, u-remote system, order no. 1550070000. A 4-channel digital input module for the u-remote system, designed to receive binary control signals from AC-powered switches, sensors, and transmitters operating at mains voltage levels up to 265 V AC (VDE) or 277 V AC (UL). Each channel has its own LED status indicator, and module-level diagnosis is supported. The module's system electronics operate from the standard 24 V DC u-remote bus, providing full galvanic isolation of 500 V DC between the AC field side and the system bus. Compatible with all u-remote fieldbus head stations.
Available in stock — ships within 3 days after payment.
Product overview
| Manufacturer | Weidmüller Interface GmbH & Co. KG |
| Type | UR20-4DI-2W-230V-AC |
| Order number | 1550070000 |
| GTIN (EAN) | 4050118356380 |
| System reference | Lenze W560-C-2E-001 |
| Product type | Remote I/O module, IP20, Digital signals, Input, 4-channel, 230 V AC, PUSH IN connection |
| Module type | Digital input module — 4-channel, 2-wire, 230 V AC mains voltage input |
| Number of digital inputs | 4 |
| Sensor type compatibility | Types 1 and 3, EN 61131-2 |
| Supply voltage (input) | 277 V AC (UL), 265 V AC (VDE) |
| Input voltage, high | ≥ 80 V |
| Input voltage, low | < 65 V |
| Input frequency | 50 Hz, 60 Hz |
| Max. input frequency | 60 Hz |
| Input filter | Configurable, 10 ms |
| Line-to-line voltage between channels | 400 V permissible (multi-phase installations) |
| Sensor supply | No (externally powered AC sensors) |
| Reverse polarity protection | Yes |
| Sensor connection | 2-wire |
| Module diagnosis | Yes |
| Individual channel diagnosis | No |
| Supply voltage (system bus) | 24 V DC +20% / –15%, via system bus |
| Current consumption from Isys, typ. | 8 mA |
| Galvanic isolation | 500 V DC between the current paths |
| Type of connection | PUSH IN |
| Wire cross-section | 0.14 mm²–1.5 mm² (AWG 26–16), solid and finely stranded |
| Fieldbus protocols | PROFINET IRT/RT, PROFIBUS DP-V1, EtherCAT, Modbus/TCP, EtherNet/IP, CANopen, DeviceNet, POWERLINK, CC-Link, CC-Link IE TSN, IEC 61162-450 |
| Interface | u-remote system bus |
| Transmission speed, max. | 48 Mbit/s |
| Mounting | TS 35 DIN rail |
| Operating temperature | –20°C to +60°C |
| Storage temperature | –40°C to +85°C |
| Dimensions (W × H × D) | 11.5 mm × 120 mm × 76 mm |
| Mounting dimension – height | 128 mm |
| Net weight | 89 g |
| UL 94 flammability rating | V-0 |
| Pollution severity | 2 |
| Test voltage | 500 V |
| Surge voltage category | II |
| Vibration resistance | 5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm amplitude; 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration (IEC 60068-2-6) |
| Shock | 15 g over 11 ms, half sinus wave (IEC 60068-2-27) |
| Air humidity (operation/storage/transport) | 10% to 95%, non-condensing (DIN EN 61131-2) |
| Air pressure (operation) | ≥ 795 hPa (height ≤ 2000 m, DIN EN 61131-2) |
| RoHS compliance | Compliant with exemption (7a, 7cI) |
| REACH SVHC | Lead 7439-92-1 |
| Product Carbon Footprint | 8.705 kg CO₂ eq. (cradle to gate) |
| Approvals / certifications | CE, UKCA, cULus (E141197), cULusEX (E223527), ATEX, IECEx, ClassNK, ABS, DNV, KoreaCert, RoHS compliant |
| Condition | New — in original packaging (OVP) |
Applications
- Direct acquisition of mains-voltage AC switching signals in machine and plant engineering — the module accepts binary input signals from 230 V AC-powered mechanical switches, pushbuttons, cam switches, and relay contacts without requiring external signal converters or intermediate relay modules, simplifying cabinet design in installations where AC-voltage field devices are already installed
- Multi-phase AC installations — line-to-line voltages of up to 400 V are permissible between individual channels, enabling all four inputs to be connected to different phases of a three-phase supply simultaneously, which is particularly useful for monitoring multi-phase motor contactors, phase-presence detection, and mains-voltage interlocking circuits
- Mixed 24 V DC and 230 V AC I/O architectures — by integrating the module into a standard u-remote station alongside 24 V DC I/O modules, engineers can avoid separate AC input expansion units or dedicated AC PLC racks, consolidating all I/O onto a single fieldbus-connected station and reducing overall hardware count
- Replacement of legacy discrete AC input cards in modernisation projects — the module provides a direct fieldbus-connected alternative to traditional hard-wired AC relay input panels and older PLC AC input cards, enabling migration to modern decentralised I/O without rewiring existing AC field devices
- Hazardous area installations (ATEX/IECEx) and marine applications (ClassNK, ABS, DNV) requiring a certified 230 V AC digital input module within the u-remote platform, compatible with all u-remote fieldbus head stations
Shipping
- Ships within 3 days after payment
- Secure packaging for safe industrial transport
- Free delivery within Germany
Warranty & compliance
- 12-month warranty included
- Product is fully compliant with EU industry standards
- VAT invoice included with every order
(GPSR (EU) 2023/988): Contact us at info@liquisto.com for Manufacturer / EU Responsible Party product safety contact details.