{"product_id":"weidmuller-ur20-4ai-rtd-diag-copy","title":"Weidmüller UR20-3EM-230V-AC","description":"\u003cp\u003eWeidmüller UR20-3EM-230V-AC \/ Lenze W510-C-MT-001 — 3-channel power measurement module, 1 or 3 phases, rated voltage up to 300 Veff AC, 16-bit resolution, PUSH IN, IP20, u-remote system, order no. 2007420000. A power measurement module for the u-remote system that measures and processes currents and voltages of single-phase or three-phase loads at rated voltages up to 300 Veff AC (phase and neutral conductor) and 520 Veff line-to-line. Active, reactive, apparent and harmonic power, energy consumption, phase angle and many further electrical parameters are calculated directly within the module at 16-bit resolution (internal 24-bit) with a measurement accuracy of 0.5% of final value for voltage and current and 1% for calculated values. The module integrates into existing automation solutions via the u-remote system and is configurable via Micro USB 2.0. Compatible with all u-remote fieldbus head stations.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eAvailable in stock\u003c\/strong\u003e — ships within 3 days after payment.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003ePlease note:\u003c\/strong\u003e This article has been announced as discontinued and will no longer be available after 31 December 2026. The recommended alternative product is the UR20-3EM-400V-AC-CT1A.\u003c\/p\u003e\n\u003ch3\u003eProduct overview\u003c\/h3\u003e\n\u003ctable style=\"width: 100%; border-collapse: collapse; font-size: 12px;\"\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eManufacturer\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eWeidmüller Interface GmbH \u0026amp; Co. KG\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eType\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eUR20-3EM-230V-AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eOrder number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e2007420000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMaterial number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e2988950000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eGTIN (EAN)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e4050118392777\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eSystem reference\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eLenze W510-C-MT-001\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eProduct type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eRemote I\/O module, IP20, 6-channel, Input, Power measurement, PUSH IN connection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eModule type\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eFunctional module — 3-channel power measurement, 1 or 3 phases, AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eNumber of measurement inputs\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eRated voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e300 Veff (L-N), 520 Veff (L-L)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eNominal load capacity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e0…1 A \/ 0…5 A AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eResolution\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e16 bit per channel (internal 24 bit)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMeasurement accuracy\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e0.5% of final value (U\/I); 1% for calculated values\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMeasurement method\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eHigh Resolution Delta Sigma (current measurement in outer conductor)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eSampling rate of current measurement\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e3,300 samples\/s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eFrequency of supply system\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e45…65 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eAnalysis of harmonics\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e31 (Blackmann-Harris Window)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eConnectable converter ratios\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e1 … 1000\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMeasurement resistance (shunt)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e4 mΩ (at 5 A), 20 mΩ (at 1 A)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eInput impedance voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e2.4 MΩ per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eNominal peak voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e4 kV\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eCategory for voltage measurements\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eCAT II (IEC 61010 Part 1)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eInsulation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e1.5 kVeff (input \/ system)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eModule diagnosis\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eYes\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eProcess data\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e32 Byte\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eConfiguration interface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eMicro USB 2.0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eSupply voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e24 V DC +20% \/ –15%, via system bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eCurrent consumption from Isys, typ.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e8 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eCurrent consumption from IIN\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e12 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eGalvanic isolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e500 V DC between the current paths\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eType of connection\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003ePUSH IN\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eWire cross-section\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e0.14 mm²–1.5 mm² (AWG 26–16), solid and finely stranded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eFieldbus protocols\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003ePROFINET IRT\/RT, PROFIBUS DP-V1, EtherCAT, Modbus\/TCP, EtherNet\/IP, CANopen, DeviceNet, POWERLINK, CC-Link, CC-Link IE TSN, IEC 61162-450\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eInterface\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eu-remote system bus\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eTransmission speed, max.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e48 Mbit\/s\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMounting\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eTS 35 DIN rail\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eOperating temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e–20°C to +60°C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eStorage temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e–40°C to +85°C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eDimensions (W × H × D)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e11.5 mm × 120 mm × 76 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eMounting dimension – height\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e128 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eNet weight\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e90 g\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eUL 94 flammability rating\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eV-0\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003ePollution severity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eTest voltage\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e500 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eSurge voltage category\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eII\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eVibration resistance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm amplitude; 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration (IEC 60068-2-6)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eShock\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e15 g over 11 ms, half sinus wave (IEC 60068-2-27)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eAir humidity (operation\/storage\/transport)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e10% to 95%, non-condensing (DIN EN 61131-2)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eAir pressure (operation)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e≥ 795 hPa (height ≤ 2000 m, DIN EN 61131-2)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eRoHS compliance\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eCompliant with exemption (7a, 7cI)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eREACH SVHC\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eLead 7439-92-1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eProduct Carbon Footprint\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003e8.889 kg CO₂ eq. (cradle to gate)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eApprovals \/ certifications\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eCE, UKCA, cULus (E141197), cULusEX (E223527), RoHS compliant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eDelivery status\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eDiscontinuation announced — available until 31 December 2026. Alternative: UR20-3EM-400V-AC-CT1A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px 8px; width: 40%;\"\u003e\u003cstrong\u003eCondition\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd style=\"padding: 6px 8px;\"\u003eNew — in original packaging (OVP)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003ch3\u003eApplications\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSingle-phase and three-phase power monitoring in machine and plant engineering — the module measures active, reactive, apparent and harmonic power, energy consumption and phase angle directly at rated voltages up to 300 Veff (L-N) and 520 Veff (L-L) in both single-phase and three-phase configurations, delivering comprehensive power quality data within a single 11.5 mm wide u-remote slot without a separate power analyser\u003c\/li\u003e\n\u003cli\u003eHarmonic analysis and power quality measurement — up to 31 harmonics are analysed per measurement cycle using the Blackmann-Harris Window method at a sampling rate of 3,300 samples\/s, enabling detection of harmonic distortion from variable frequency drives, switching power supplies and other non-linear loads in automated production environments\u003c\/li\u003e\n\u003cli\u003eNon-invasive retrofit integration using conversion current transformers — currents above 5 A can be measured using Weidmüller plug-on or split-core current measuring transducers with converter ratios of 1 to 1000, allowing the module to be added to existing installations without cutting primary conductors or interrupting the load circuit during commissioning\u003c\/li\u003e\n\u003cli\u003eFieldbus-integrated energy management — the 32 bytes of process data transmitted per cycle, selectable via parameters for the relevant fieldbus, allow energy consumption and power quality data to be fed directly into PLC-based energy management systems across PROFINET, EtherCAT, PROFIBUS, Modbus\/TCP, EtherNet\/IP and other protocols supported by u-remote head stations\u003c\/li\u003e\n\u003cli\u003eIntegration into Lenze machine automation systems — as the Lenze W510-C-MT-001 system reference, the module connects power measurement capability directly into Lenze automation architectures, enabling coordinated monitoring of drive and load energy data alongside motion control and I\/O functions on a shared fieldbus network\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eShipping\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eShips within 3 days after payment\u003c\/li\u003e\n\u003cli\u003eSecure packaging for safe industrial transport\u003c\/li\u003e\n\u003cli\u003eFree delivery within Germany\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eWarranty \u0026amp; compliance\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e12-month warranty included\u003c\/li\u003e\n\u003cli\u003eProduct is fully compliant with EU industry standards\u003c\/li\u003e\n\u003cli\u003eVAT invoice included with every order\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e(GPSR (EU) 2023\/988): Contact us at \u003ca href=\"mailto:info@liquisto.com\"\u003einfo@liquisto.com\u003c\/a\u003e for Manufacturer \/ EU Responsible Party product safety contact details.\u003c\/p\u003e","brand":"WEIDMUELLER","offers":[{"title":"Default Title","offer_id":57776975446280,"sku":"LNZ-13642267","price":299.99,"currency_code":"EUR","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0574\/7566\/1973\/files\/WeidmullerUR20-3EM-230V-AC.jpg?v=1778570409","url":"https:\/\/liquistoaxcess.com\/nl-eu\/products\/weidmuller-ur20-4ai-rtd-diag-copy","provider":"LiquistoAxcess","version":"1.0","type":"link"}