Product Details

Weidmüller UR20-4AI-RTD-DIAG / Lenze W540-C-2E-012 — 4-channel RTD analogue input module, resistance temperature detector, 16-bit resolution, individual channel diagnosis, 50/60 Hz suppression, PUSH IN, IP20, u-remote system, order no. 1315700000. A 4-channel temperature input module for the u-remote system, the module detects cable breaks and over/under-range values via individual channel diagnosis. Automatic 50 Hz to 60 Hz interference suppression and an adjustable conversion time of 36 to 240 ms are included. Sensors connect via 2-wire, 3-wire or 4-wire PUSH IN terminals to support a wide range of RTD wiring configurations. The module electronics supply connected sensors from the input current path (UIN). Compatible with all u-remote fieldbus head stations.

Available in stock — ships within 3 days after payment.

Product overview

Manufacturer Weidmüller Interface GmbH & Co. KG
Type UR20-4AI-RTD-DIAG
Order number 1315700000
GTIN (EAN) 4050118118872
System reference Lenze W540-C-2E-012
Product type Remote I/O module, IP20, Analog signals, Temperature, RTD, 4-channel, PUSH IN connection
Module type Temperature module — 4-channel RTD input, 16-bit, diagnostics
Number of analogue inputs 4
RTD types supported Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, 40 Ω, 80 Ω, 150 Ω, 300 Ω, 500 Ω, 1 kΩ, 2 kΩ, 4 kΩ
Resolution 16 Bit
Accuracy 0.2% FSR / 0.3% FSR for Ni sensors / 0.6% FSR for Cu10
Measured temperature range –200°C to +850°C
Conversion time Adjustable, 36…240 ms
Temperature coefficient ≤ 50 ppm/K
Internal resistance U 1 MΩ
Reverse polarity protection Yes
Module diagnosis Yes
Individual channel diagnosis Yes
Sensor connection 2-wire, 3-wire, 4-wire
Process data 8 Byte
Parameter data 32 Byte
Diagnostic data 20 Byte
Supply voltage 24 V DC +20% / –15%, via system bus
Current consumption from Isys, typ. 8 mA
Current consumption from IIN <20 mA
Galvanic isolation 500 V DC between the current paths
Type of connection PUSH IN
Wire cross-section 0.14 mm²–1.5 mm² (AWG 26–16), solid and finely stranded
Fieldbus protocols PROFINET IRT/RT, PROFIBUS DP-V1, EtherCAT, Modbus/TCP, EtherNet/IP, CANopen, DeviceNet, POWERLINK
Interface u-remote system bus
Transmission speed, max. 48 Mbit/s
Mounting TS 35 DIN rail
Operating temperature –20°C to +60°C
Storage temperature –40°C to +85°C
Dimensions (W × H × D) 11.5 mm × 120 mm × 76 mm
Mounting dimension – height 128 mm
Net weight 91 g
UL 94 flammability rating V-0
Pollution severity 2
Test voltage 500 V
Surge voltage category II
Vibration resistance 5 Hz ≤ f ≤ 8.4 Hz: 3.5 mm amplitude; 8.4 Hz ≤ f ≤ 150 Hz: 1 g acceleration (IEC 60068-2-6)
Shock 15 g over 11 ms, half sinus wave (IEC 60068-2-27)
Air humidity (operation/storage/transport) 10% to 95%, non-condensing (DIN EN 61131-2)
Air pressure (operation) ≥ 795 hPa (height ≤ 2000 m, DIN EN 61131-2)
RoHS compliance Compliant with exemption (7a, 7cI)
REACH SVHC Lead 7439-92-1
Product Carbon Footprint 8.684 kg CO₂ eq. (cradle to gate)
Approvals / certifications CE, UKCA, cULus (E141197), cULusEX (E223527), ATEX, IECEx, ClassNK, ABS, DNV, KoreaCert, RoHS compliant
Condition New — in original packaging (OVP)

Applications

  • Multi-type RTD temperature measurement in machine and plant engineering — a single module accepts all common Pt, Ni and Cu resistance temperature detector types as well as fixed resistance inputs from 40 Ω to 4 kΩ across a measurement range of –200°C to +850°C, eliminating the need for separate modules for different RTD families in mixed-sensor installations such as motor windings, HVAC systems, food processing equipment and pharmaceutical processes
  • High-accuracy temperature acquisition with 2-, 3- and 4-wire lead compensation — 16-bit resolution and 0.2% FSR accuracy for Pt sensors are combined with selectable 2-wire, 3-wire and 4-wire connection modes, allowing lead resistance errors to be fully compensated in 3- and 4-wire configurations for precise absolute temperature measurement over long cable runs
  • Cable break and out-of-range detection via individual channel diagnosis — each channel independently monitors sensor integrity and measurement limits, providing 20 bytes of diagnostic data that enable rapid fault localisation down to the channel level without interrupting other channels, supporting high-availability process monitoring applications
  • Suppression of mains interference in AC-powered installations — automatic 50 Hz to 60 Hz interference suppression eliminates the dominant AC noise source from RTD signal paths, ensuring stable and accurate temperature readings even when sensor wiring runs close to power cables, frequency inverters or switchgear in industrial cabinets
  • Hazardous area and marine temperature monitoring — ATEX, IECEx, ClassNK, ABS and DNV certifications alongside reverse polarity protection make the module suitable for certified RTD temperature acquisition in offshore, marine and Ex-zone environments within mixed u-remote I/O stations compatible with PROFINET, EtherCAT, PROFIBUS, Modbus/TCP, EtherNet/IP and other supported fieldbus protocols

Shipping

  • Ships within 3 days after payment
  • Secure packaging for safe industrial transport
  • Free delivery within Germany

Warranty & compliance

  • 12-month warranty included
  • Product is fully compliant with EU industry standards
  • VAT invoice included with every order

(GPSR (EU) 2023/988): Contact us at info@liquisto.com for Manufacturer / EU Responsible Party product safety contact details.