Product Details

Beckhoff EL3062-0030 2-Channel Analog Input Terminal — 0–30 V, Single-Ended, 12-bit, EtherCAT, 500 V Isolation, IP20, CE/UL/ATEX, ATEX II 3G Ex nA IIC T4 Gc. Special variant of the EL3062 with extended input range up to 30 V (standard EL3062 is 0–10 V). 

Available in stock — ships within 3 days after payment.

Product overview

Part number EL3062-0030
Product type 2-channel analog input terminal, EtherCAT
Signal voltage 0–30 V (special variant; standard EL3062: 0–10 V)
Number of inputs 2 (single-ended)
Resolution 12 bit (16-bit process image incl. sign)
Measuring error < ±0.3 % (relative to full scale value)
Conversion time 0.625 ms (default, configurable, multiplex)
Input filter limit frequency 1 kHz
Internal resistance > 130 kΩ
Dielectric strength max. 30 V
Electrical isolation 500 V (E-bus / signal voltage)
Power supply Via E-bus
Current consumption (E-bus) Typ. 130 mA
Bit width in process image Inputs: 8 byte
Special features Activatable FIR/IIR filters, limit value monitoring
Degree of protection IP20
ATEX marking II 3 G Ex nA IIC T4 Gc
Approvals CE, UL, ATEX
EMC EN 61000-6-2 (immunity) / EN 61000-6-4 (emission)
Vibration / shock resistance EN 60068-2-6 / EN 60068-2-27
Operating temperature –25 to +60 °C
Storage temperature –40 to +85 °C
Relative humidity 95%, non-condensing
Wiring Pluggable — compatible with all ESxxxx terminals
Weight Approx. 60 g
Condition New in original packaging (OVP)

Applications

  • Acquisition of 0–30 V analog signals from sensors and transducers in EtherCAT-based control systems
  • Voltage monitoring and process value measurement in machine automation and industrial control panels
  • Hazardous area installations requiring ATEX-rated EtherCAT I/O terminals (Zone 2)
  • Applications requiring configurable digital filtering (FIR/IIR) and programmable limit value monitoring

Shipping

  • Ships within 3 days after payment
  • Secure packaging for safe delivery
  • Free delivery within Germany

Warranty & compliance

  • 12-month warranty included
  • Product is fully compliant with EU industry standards
  • VAT invoice included with every order

(GPSR (EU) 2023/988): Contact us at info@liquisto.com for Manufacturer/EU Responsible Party product safety contact details.